MIK-ST500 Temperature transmitter programmable
-
Specification
Input | |
Input signal | Resistance temperature detector (RTD),thermocouple (TC), and linear resistance. |
Cold-junction compensation temperature scope | -20~60℃ |
Compensation precision | ±1℃ |
Output | |
Output signal | 4-20mA |
Load resistance | RL≤(Ue-12)/0.021 |
Output current of upper and lower limit overflow alarm | IH=21mA, IL=3.8mA |
Output current of input disconnection alarm | 21mA |
Power supply | |
Supply voltage | DC12-40V |
Other parameters | |
Transmission precision (20℃) | 0.1%FS |
Temperature drift | 0.01%FS/℃ |
Response time | Reach to 90% of the final value for 1s |
Used environmental temperature | -40~80℃ |
Storage temperature | -40~100℃ |
Condensation | Allowable |
Protection level | IP00; IP66 (installation) |
Electromagnetic compatibility | Conform to GB/T18268 industrial equipmentapplication requirements(IEC 61326-1) |
Input Type Table
Model | Type | Measurement scope | Minimum measurement scope |
Resistance temperaturedetector (RTD) | Pt100 | -200~850℃ | 10℃ |
Cu50 | -50~150℃ | 10℃ | |
Thermocouple (TC) | B | 400~1820℃ | 500℃ |
E | -100~1000℃ | 50℃ | |
J | -100~1200℃ | 50℃ | |
K | -180~1372℃ | 50℃ | |
N | -180~1300℃ | 50℃ | |
R | -50~1768℃ | 500℃ | |
S | -50~1768℃ | 500℃ | |
T | -200~400℃ | 50℃ | |
Wre3-25 | 0~2315℃ | 500℃ | |
Wre5-26 | 0~2310℃ | 500℃ |
-
Product size
-
Product wiring
Note: no 24V power supply is required when using the V8 serial port programming line
-
Software
SUP-ST500 temperature transmitter supports input signal adjustment. If you need to adjust the input signal, please let us know and we will give you software.
With the software, you can adjust the temperature type, such as PT100, Cu50, R, T, K etc; input temperature range.
Write your message here and send it to us